Model(s): CPD 2500, CPD 3000, CPD 3500, CPD 4000, CPD 5000, CPD 6000, CPD 7000, CPD 8000, CPD 9000, CPD 10000, CPD 12000, CPD 15000, CPD 20000, CPD 25000, CPD 30000
*Scroll to the right on mobile to see entire chart
Model |
Inlet & Outlet Flanged |
scfm(1) |
Nm3/h(1) |
absorbed power kW |
absorbed power amps |
compressor(s) Qty (hp) |
CPD 2500 |
4" |
2,500 |
4,248 |
9.7 |
33 |
1 (13 hp) |
CPD 3000 |
6" |
3,000 |
5,097 |
12 |
36 |
1 (15 hp) |
CPD 3500 |
6" |
3,500 |
5,947 |
15 |
37 |
2 (10 hp) |
CPD 4000 |
6" |
4,000 |
6,796 |
15 |
45 |
2 (10 hp) |
CPD 5000 |
8" |
5,000 |
8,495 |
19 |
50 |
2 (13 hp) |
CPD 6000 |
8" |
6,000 |
10,194 |
22 |
50 |
3 (10 hp) |
CPD 7000 |
8" |
7,000 |
11,893 |
26 |
65 |
3 (13 hp) |
CPD 8000 |
10" |
8,000 |
13,592 |
30 |
71 |
4 (10 hp) |
CPD 9000 |
10" |
9,000 |
15,291 |
36 |
80 |
5 (10 hp) |
CPD 10000 |
10" |
10,000 |
16,990 |
38 |
91 |
1 (50 hp) |
CPD 12000 |
12" |
12,000 |
20,388 |
45 |
97 |
1 (60 hp) |
CPD 15000 |
12" |
15,000 |
25,485 |
60 |
138 |
2 (40 hp) |
CPD 20000 |
14" |
20,000 |
33,980 |
75 |
175 |
2 (50 hp) |
CPD 25000 |
16" |
25,000 |
42,475 |
93 |
186 |
1 (120 hp) |
CPD 30000 |
18" |
30,000 |
50,970 |
112 |
195 |
1 (150 hp) |
(1) in compliance with ADF 100 specifications for compressed air dryers: Inlet temperature: 100°F, ambient temperature: 100°F, inlet pressure: 100 psig, pressure dew point: 33°F to 39°F. For all other conditions refer to the correction factors.
(2) nominal absorbed power at rated operating conditions using 460/3/60 power supply (as applicable). For absorbed power at other voltages or conditions, mdi at 727-835-0678
*Scroll to the right on mobile to see entire chart
Specifications |
CPD 2500 to 9000 |
CPD 10000 to 30000 |
compressor type |
scroll |
semi-hermetic |
heat exchanger type |
stainless steel |
shell & tube (ASME) |
design operating pressure range |
0 to 150 psig |
design inlet air temperature range |
40 to 140°F |
design ambient temperature range |
40 to 120°F |
condenser cooling options |
water-cooled (standard) or air-cooled (optional) |
refrigerant type |
R404a |
control panel enclosure |
NEMA 12 |
system pressure drop |
3.5 to 4.5 psid |
➤Click Here for Pressure, dew point & Temperature Correction Factors Chart
How It Works
1. air inlet
2. air outlet
3. pre-cooler/re-heater
4. air-to-air/glycol heat exchanger
5. moisture separator
6. evaporator
7. cold bank storage
8. pump
9. isolation valves
10. solenoid valve
11. defroster
12. compressor
13. suction accumulator
14. condenser
15. filter dryer
16. sight glass
17. thermostatic expansion valve
Options
• Optional 575 V, 3 phase, 60 hz available
*Scroll to the right on mobile to see entire chart
Model |
Width (in) |
Depth (in) |
Height (in) |
Weight (lbs) |
CPD 2500 |
52" |
60" |
60" |
3,400 |
CPD 3000 |
52" |
60" |
60" |
3,600 |
CPD 3500 |
60" |
130" |
70" |
3,900 |
CPD 4000 |
60" |
130" |
70" |
4,200 |
CPD 5000 |
60" |
130" |
75" |
6,000 |
CPD 6000 |
70" |
130" |
75" |
7,200 |
CPD 7000 |
80" |
135" |
77" |
8,600 |
CPD 8000 |
82" |
140" |
80" |
9,800 |
CPD 9000 |
85" |
145" |
80" |
12,200 |
CPD 10000 |
85" |
145" |
80" |
12,500 |
CPD 12000 |
90" |
160" |
80" |
13,800 |
CPD 15000 |
90" |
180" |
85" |
17,000 |
CPD 20000 |
100" |
200" |
85" |
21,500 |
CPD 25000 |
120" |
210" |
87" |
23,000 |
CPD 30000 |
125" |
230" |
90" |
27,000 |
Click Here to view the mdi Line Sheet.